How to Design Novec 1230 Fire Suppression System: A Step-by-Step Guide
In the world of fire protection, clean agent systems have become the go-to choice for protecting sensitive environments where water or foam might do more harm than good. One of the most popular agents today is Novec 1230, a sustainable, electrically non-conductive, and residue-free suppressant developed by 3M. But how exactly do you go about designing a Novec 1230 fire suppression system that’s both effective and compliant?
In this blog, we’ll break down the design process into manageable steps, giving you both the technical insight and practical considerations needed to design a robust Novec 1230 system.
1. Understand the Application Environment
Before jumping into calculations or hardware, assess what you’re protecting:
- Is it a data center, control room, archive, or telecommunication hub?
- Are there any air handling systems or HVAC units that could affect agent dispersion?
- What is the ceiling height and room volume?
This initial site survey helps you determine the scope and sensitivity of the protection system.
2. Identify Design Standards
Designing a Novec 1230 system isn’t just about spraying gas—it’s a regulated process. Use recognized standards such as:
- NFPA 2001: Standard on Clean Agent Fire Extinguishing Systems
- ISO 14520: International Standard for Gaseous Fire-Extinguishing Systems
These standards provide detailed guidelines on minimum agent concentrations, hold times, system testing, and room integrity.
3. Calculate Room Volume Accurately
Measure the length, width, and height of the enclosure. This will allow you to calculate the total volume (in cubic meters or feet), which directly affects how much Novec 1230 is needed.
VOLUME= Length x Width x Height
Also, take note of:
- False ceilings or raised floors
- Obstructions or partitions
- Leakage paths (doors, vents)
Even small discrepancies in volume can result in under- or over-pressurization, which could compromise the system’s effectiveness.
4. Determine Agent Quantity
Novec 1230 typically requires a minimum design concentration of 4.5% to 6% by volume for Class A hazards (ordinary combustibles), but this may vary based on your specific application.
Use software tools (often provided by manufacturers) to run agent flow calculations. These programs factor in room volume, temperature, nozzle placement, pipe routing, and discharge time to determine:
- Total agent mass
- Cylinder count and size
- Distribution network
Always cross-verify with NFPA or ISO concentration tables.
We can use these two formulas to find out the minimum required amount of NOVEC 1230:
Formula 1:
W = V * C.F. * F.F.
W = weight of agent
V = volume of the protected enclosure
F.F. = flooding factor
C.F. = atmospheric correction factor
Formula 2:

s = 0.0664 + 0.0002741*t
W = weight of agent
V = volume of the protected enclosure
C.F. = atmospheric correction factor
s = specific volume of superheated Novec 1230 fluid vapor
t = design temperature in the hazard area
C = concentration of agent required
This calculation includes an allowance for the normal leakage from a “tight” enclosure due to agent expansion.
With the hazard classification already determined, the next step is to calculate the amount of Novec 1230 agent needed to achieve the appropriate design concentration. For instance, based on the reference chart below, a concentration of 4.2% can be used for protecting Class A or Class C fire hazards.

Now calculation from Flooding Factors Table Step by Step

- W/V (Agent Needed per m³): This tells us how much Novec 1230 (in kilograms) is required for each cubic meter of space to reach the right concentration level at a certain temperature.
2. t (Temperature in °C): This is the temperature inside the area you’re protecting. It affects how the agent behaves when released.
3. s (Specific Volume): This shows how much space the Novec 1230 vapor takes up. You can estimate it using this simple formula:
s = 0.1269 + 0.0005 × temperature (°C)
4. C (Concentration %): This is the percentage of Novec 1230 needed in the air to effectively put out a fire at the given temperature.
NOVEC 1230 ATMOSPHERE CORRECTION FACTOR (C.F)

5. Select and Position Nozzles
Nozzles play a critical role in achieving uniform distribution. Proper placement ensures:
- No “dead zones” in agent coverage
- Proper droplet size and spray pattern
- Minimal noise or turbulence during discharge
Key considerations:
- Mounting height
- Distance from walls or obstructions
- Coverage radius (usually specified per nozzle type)
Nozzle Installation
There are two basic System nozzle configurations:
- The 360° nozzle, which provides a full 360° discharge pattern designed for placement in the center
of the hazard. - The 180° nozzle, which provides a 180° discharge pattern designed for placement adjacent to a side wall
of the hazard.
All nozzles require the installation of a dirt trap comprising 1 side tee, 2 nipples, and 1 pipe cap. Fit the nozzle to the nipple on the dirt trap and check the nozzle orifice to ensure proper orientation. Dirt trap lengths should be no more than 10 times nominal pipe
diameter.
A false ceiling comprising loose tiles must have the tiles retained within a 2.0 m (6.5ft) radius of the nozzle, to prevent movement during system discharge. Nozzles should be installed a maximum of 370 mm (14.5″) below the ceiling.
After the system piping has been blown free of debris, install the discharge nozzles in strict accordance with the system drawings. Orient the nozzles as shown on drawings. Make certain that the correct nozzle type, part number and orifice size are installed in the proper location.

6. Design the Piping Network
The piping system needs to deliver the agent from the cylinder to the nozzles within 10 seconds (as per NFPA 2001). Use:
- Schedule 40 or Schedule 80 pipe (based on pressure requirements)
- Minimal bends to reduce pressure drop
- Flow calculations to determine pipe diameters
Some designers use CAD-based hydraulic calculation tools to model the piping layout for accuracy.
Pipe Installation
In general, the installation should commence at the union elbow / manifold assembly and progress along to the
discharge nozzles. Install the Pipework to the installation drawings provided, ensuring that the following is
adhered to:
The piping material must conform to the requirements of NFPA 2001 4.2.1.
The pipe must be reamed, blown clear and swabbed with an appropriate solvent to remove mill varnish
and cutting oil before assembly as required by NFPA 2001 4.2.1.
PTFE (Teflon) tape is the only acceptable pipe sealant and must be applied to the male threads.

7. Integrate Detection and Control Panels
Early detection is key. A typical Novec 1230 system is paired with:
- Aspirating smoke detectors (VESDA) for high sensitivity
- Control panels that manage alarms, pre-discharge delays, and agent release
- Abort switches and manual release stations near exits
Ensure your detection system meets the room’s risk profile and provides a reliable trigger for the suppression system.
8. Ensure Room Integrity and Pressure Relief
A clean agent system is only effective if the room can contain the agent for a minimum hold time (usually 10 minutes).
- Perform a Door Fan Test (Room Integrity Test) to confirm leakage levels
- Install pressure relief vents to prevent structural damage from pressure spikes during discharge
Neglecting room integrity is one of the most common reasons for system failure.
9. Conduct Testing and Commissioning
Before going live, perform:
- Functional testing of detection and control systems
- Discharge simulation or verification
- Training for staff and end users on emergency procedures
Also, document everything — system drawings, calculation reports, cylinder certifications, and testing results.
10. Plan for Maintenance and Refill
Novec 1230 systems are low-maintenance, but they still require:
- Annual inspections
- Cylinder pressure checks
- Post-discharge refills and recalibration
Make sure you have a service agreement in place with a certified fire protection company.
Conclusion
Designing a Novec 1230 fire suppression system requires both technical expertise and real-world foresight. From careful room assessments to detailed agent calculations and system testing, every step matters. When done right, Novec 1230 systems offer clean, effective fire suppression without the collateral damage.
Whether you’re a designer, consultant, or facility manager, understanding these fundamentals can help you ensure safety, compliance, and peace of mind.
